TDI NITRO-GEN® Nitrogen Generator - Operating Instructions

Quick Start Guide

WARNING! - Read all instructions in the supplied user guide before installing and using your NITRO-GEN Nitrogen Generator.
WARNING! - The NITRO-GEN® Nitrogen Generator system can contain pressurized gas.  Pressurized gas may cause injury if you use or handle it inappropriately.  Read and follow the safety instructions below.
If you do not understand any part of the safety warnings or operating instructions, call TDI International, Inc. for assistance.  You can reach a customer service representative at 520-799-8000.
  • Read and keep the supplied user guide in a convenient location for future use (a hard copy user guide is provided with every NITRO-GEN purchase).  Make this user guide available to all operators of the nitrogen generator.
  • If any statement or specification in this user guide (especially with regard to safety) does not agree with legislation or standard industry practices, the more demanding directive shall apply.
  • Direct any nitrogen vented from the generator to the outside of your facility so that it does not displace the air in the room and cause suffocation.
  • You must employ federal, state, local and your plant's safe working practices and rules when operating this generator.
  • The owner is responsible for maintaining the generator in a safe operating condition.
  • Materials that you use to maintain, assemble, and connect the generator to supporting equipment should be rated and approved for use at the pressures generated by the generator.
  • The generator remains pressurized after shutdown.  Before performing maintenance, filter changes, or opening piping, you must depressurize the system.  Depressurizing the system prevents the uncontrolled escape of high-pressure gas and possible injury.  You must wear eye and hearing protection during the depressurizing process to avoid possible injury.
  • Follow your plant's lockout program before performing maintenance on the generator.
  • Only trained maintenance technicians who are familiar with high-pressure air systems and who have read this user guide should perform maintenance on the generator.
  • Wear personal protective equipment when in the proximity of the system.
  • Never allow high-pressure gas to exhaust from an unsecured hose.  An unsecured hose my whip around and cause serious injury.  If a hose should burst during use, immediately close all isolation valves.
  • Never disable or bypass any pressure or safety valve on the generator.
Unpack your Nitrogen Generator
Perform the following actions upon delivery:

1. Inspect the container for damage. If "Tip-N-Tells" are on the container, verify tat they have not been triggered.  If triggered, notify the carrier immediately.

2. Open the container and inspect it for damage that may have occurred during transit.  If you observe damage, notify the carrier immediately.

3. Check the components against the packaging list.  If components are missing, contact TDI International, Inc. and provide the model number and the serial number of your unit.

4. Remove all packaging materials prior to operating the generator

  • Remove any shrink and bubble wrap from the piping, valves, control panel, lock out / tag out electrical box, etc.
  • Be sure that no loose parts are in the cabinet.  Secure the cabinet doors.

5. Save all packing supplies in case the equipment needs to be returned during warranty period.

What's in the Container
Your shipment should contain the following items:

Standard Equipment

  • TDI NITRO-GEN® Membrane Nitrogen Generator
  • (2) AA Batteries (packed in documentation folder)

Documentation

  • Nitrogen generator quick start guide
  • Nitrogen generator user guide
Select a Location
Install your nitrogen generator according to the recommendations below to ensure optimum performance, safe operation, and warranty coverage.

You should locate the nitrogen generator indoors and maintain an ambient air temperature around the unit of above 33ºF (0.5ºC) at all times.  The humidity of the location can range from 0-95% humidity, non-condensing.  Allow sufficient space around the generator to: a) install vent piping and access pipe connections, and b) perform maintenance.

The ground area you select as a location should be flat and stable.

Utility Requirements
Utilities should meet the requirements below to ensure optimum performance, safe operation, and warranty coverage.

Compressed Air Supply Requirements

Virtually any commercial air compressor is compatible with the NITRO-GEN® as long as it meets the compressed air supply requirements.

The compressed air entering the generator should be a approximately 70ºF (21ºC) to meet the output specification.  The generator can, however, function between 50 and 130ºF (10-55ºC) if required, though the output will vary accordingly.  The dew point of compressed air supplied to the generator must be 40ºF (5ºC) or lower.

Compressed air not meeting this dew point requirement can damage the generator and will void the warranty.  Air at temperatures higher or lower than this may cause damage not covered by the warranty.  The use of a correctly sized air dryer can ensure that the compressed air supply meets the dew point requirements.

NOTE - A compressed air receiving tank may be necessary to provide a reserve of compressed air to meet the fluctuating demands of the nitrogen generator.

NOTE - The use of a correctly sized air dryer can ensure that the compressed air supply meets the dew point requirements.

Inlet Air Pressure and Volume Requirements

The inlet air pressure requirement is 100 PSI for all NITRO-GEN® models.  If your inlet air pressure is not equal to the requirement, the nitrogen output may be above or below the system's design capability.  Inlet air pressures higher than the maximum allowable working pressure (MAWP) will damage the nitrogen generating system and void the warranty.  In addition, a given model will consume more or less compressed air depending on the desired nitrogen purity and flow rate. 

Adjustment for Altitude

Add 1% tot he feed air consumption requirement for every 300 feet above sea level.

Adjustment for Length of Air Supply Piping

The air supply piping must supply the required volume of feed air at the required pressure as measured at the generator inlet connection.  If the supply piping from the compressed air receiving tank to the generator is greater than 50 fee, increase the air supply line with one standard NPT size larger than the generator inlet size (Table 1).

Table 1. Standard NPT Pipe Sizes:

NPT Pipe Sizes (Inches)
1/4 3/8 1/2 3/4 1.0 1-1/4 1-1/2 2.0 2-1/2 3.0 4.0 6.0

Nitrogen Output Piping Requirements

Nitrogen output piping should be the same size as the nitrogen discharge piping on the generator.  If the length of the output piping connecting the generator to your process is greater than 50 feet, use piping one standard NPT size larger than the generator output line (Table 1).

Install the Membrane Nitrogen Generator
WARNING! - Materials that you use to maintain, assemble and connect the nitrogen generator to supporting equipment should be rated and approved for use at the pressures generated by the generator.
1. Move unit into place with a hand truck.

2. Install batteries for the oxygen analyzer.

3. Install any supporting equipment (including air compressor, booster, air dryer or receiving tanks) according to the manufacturer's recommendations.

4. Have a qualified pipefitter install suitable piping from:

  • The compressed air supply to the inlet of the nitrogen generator.
  • The nitrogen generator outlet to your process.
  • NOTE - use of piping sizes smaller than the recommended size will significantly decrease system performance and void the warranty.

5. Any tanks that you use in conjunction with the generator should be fitted with applicable pressure safety valves.

Startup and Shutdown Procedures
Starting the Generator

Start the air compressor per the manufacturer's instructions before starting the nitrogen generator.  Be sure that all valves from the air compressor to the generator inlet are open.

A - Set Valves to Pre-Start Positions

  • Be sure the main shutoff (compressed air inlet) valve is closed.
  • Turn the start-up purge control valve to the start-up purge position.
  • Turn the calibration control valve to the normal operation position.

B - Begin Flow Through the Generator

  • Slowly open the main shutoff (compressed air inlet) valve.
  • Turn the inlet control valve to the on position.
  • Be sure the inlet pressure regulator is set to the specification.  (The pressure is read at the gauge above it.)

C - Monitor the System Purity and Flow

  • Adjust the outlet flowmeter to the design specification.  Turn clockwise to reduce flow (counter-clockwise to increase).
  • After 3 minutes, turn the start-up purge control valve to the normal operation position
  • Press the power button ( ) on the oxygen analyzer.  Watch for the display to stabilize.
  • NOTE: If this is your first time starting the unit (or if it has come out of storage or been moved from a different elevation) calibrate the analyzer as follows:
    • Turn the calibration control valve to the calibrate position.
    • After 3 minutes, press the analyzer calibration button ( ).  It will display 20.9%.
    • Turn the calibration control valve to the normal operation position.
  • Monitor the purity of the nitrogen at the oxygen sensor display.  Subtract the value from 100 to determine purity of the nitrogen output.
  • Adjust the outlet flowmeter to the desired output.  Nitrogen purity will increase as flow in reduced.
    • Turn clockwise to reduce flow and oxygen content (counter-clockwise to increase flow and oxygen content.)
NOTE - If flow through the inlet filters becomes drastically reduced (due, for example, to excessive particulate from the air compressor) and there is an immediate need for nitrogen before a filter change can be performed, the inlet pressure regulator may be adjusted upward to as much as 95% of the inlet air pressure.  After the immediate need has been fulfilled, however, the filters should be examined and changed, as necessary.

NOTE - When power is restored after a power failure, the generator automatically resumes operation.

Shut Down
1. Slowly close the main shutoff (compressed air inlet) valve.

2. Turn the inlet control valve to the off position.

3. Turn the start-up purge control valve to the off position.

4. Turn the calibration control valve to the off position.

5. Press the power button ( ) on the oxygen analyzer.

6. Stop the compressor.

WARNING! - The generator remains pressurized after shutdown.  Before performing maintenance or opening any lines you must depressurize the system to prevent injury.
Depressurizing the System
WARNING! - You must wear eye and hearing protection during the depressurizing process to avoid possible injury.
Follow these steps before performing system maintenance.

1. Wear eye and hearing personal protection equipment.

2. Close the main shutoff (compressed air inlet) valve.

3. Turn the inlet control valve to the on position.

4. Turn the start-up purge control valve to the start-up purge position.

5. Be sure the inlet pressure gauge reads zero.

6. Turn the inlet control valve to the off position.

7. Turn the start-up purge control valve to the normal operation position.

Phone: (520) 799-8000 | Email: sales@tdiinternational.com  © Copyright 2000-2012 TDI International, Inc.

TDI Home  |  Catalog  |  Newsletter  |  Terms  |  Privacy Policy  |  Contact Us  |  Conversion Charts  |  Site Map

TDI International - Desiccators, Tweezers & Handtools for Cleanrooms, Labs, Electronics Assembly
Products Catalog Newsletter About Us Contact Us Site Map

TDI Home

HANDTOOLS:
 Cutters
 Cutter & Plier Kits
 Diamond Scribes
 Micro Mini Tools
 Micro Shears
 Mirrors
 Pin Vises
 Pliers
 Scalpels
 Scissors
 Screwdrivers
 Spatulas & Probes
 Tweezers
 Tweezer Kits
 Vacuum Pick Up
 Wire Crimpers
 Wire Strippers
 
EQUIPMENT:
 Chairs
 Desiccators
 Dispensers
 Gloveboxes
 Nitrogen Generators
 Nitro-Save®
 Shelving Units
 Workstations