TDI NITRO-GEN® Nitrogen Generator - Operating Instructions | |||||||||||||||||||||||||
![]() | WARNING! - Read all instructions in the supplied user guide before installing and using your NITRO-GEN Nitrogen Generator. | ||||||||||||||||||||||||
![]() | WARNING! - The NITRO-GEN® Nitrogen Generator system can contain pressurized gas. Pressurized gas may cause injury if you use or handle it inappropriately. Read and follow the safety instructions below. | ||||||||||||||||||||||||
If you do not understand any part of the safety warnings or operating instructions, call TDI International, Inc. for assistance. You can reach a customer service representative at 520-799-8000.
| |||||||||||||||||||||||||
| Unpack your Nitrogen Generator | |||||||||||||||||||||||||
| Perform the following actions upon delivery:
1. Inspect the container for damage. If "Tip-N-Tells" are on the container, verify tat they have not been triggered. If triggered, notify the carrier immediately. 2. Open the container and inspect it for damage that may have occurred during transit. If you observe damage, notify the carrier immediately. 3. Check the components against the packaging list. If components are missing, contact TDI International, Inc. and provide the model number and the serial number of your unit. 4. Remove all packaging materials prior to operating the generator
5. Save all packing supplies in case the equipment needs to be returned during warranty period. | |||||||||||||||||||||||||
| What's in the Container | |||||||||||||||||||||||||
| Your shipment should contain the following items:
Standard Equipment
Documentation
| |||||||||||||||||||||||||
| Select a Location | |||||||||||||||||||||||||
| Install your nitrogen generator according to the recommendations below to ensure optimum performance, safe operation, and warranty coverage.
You should locate the nitrogen generator indoors and maintain an ambient air temperature around the unit of above 33ºF (0.5ºC) at all times. The humidity of the location can range from 0-95% humidity, non-condensing. Allow sufficient space around the generator to: a) install vent piping and access pipe connections, and b) perform maintenance. The ground area you select as a location should be flat and stable. | |||||||||||||||||||||||||
| Utility Requirements | |||||||||||||||||||||||||
| Utilities should meet the requirements below to ensure optimum performance, safe operation, and warranty coverage.
Compressed Air Supply Requirements Virtually any commercial air compressor is compatible with the NITRO-GEN® as long as it meets the compressed air supply requirements. The compressed air entering the generator should be a approximately 70ºF (21ºC) to meet the output specification. The generator can, however, function between 50 and 130ºF (10-55ºC) if required, though the output will vary accordingly. The dew point of compressed air supplied to the generator must be 40ºF (5ºC) or lower. Compressed air not meeting this dew point requirement can damage the generator and will void the warranty. Air at temperatures higher or lower than this may cause damage not covered by the warranty. The use of a correctly sized air dryer can ensure that the compressed air supply meets the dew point requirements. NOTE - A compressed air receiving tank may be necessary to provide a reserve of compressed air to meet the fluctuating demands of the nitrogen generator. NOTE - The use of a correctly sized air dryer can ensure that the compressed air supply meets the dew point requirements. Inlet Air Pressure and Volume Requirements The inlet air pressure requirement is 100 PSI for all NITRO-GEN® models. If your inlet air pressure is not equal to the requirement, the nitrogen output may be above or below the system's design capability. Inlet air pressures higher than the maximum allowable working pressure (MAWP) will damage the nitrogen generating system and void the warranty. In addition, a given model will consume more or less compressed air depending on the desired nitrogen purity and flow rate. Adjustment for Altitude Add 1% tot he feed air consumption requirement for every 300 feet above sea level. Adjustment for Length of Air Supply Piping The air supply piping must supply the required volume of feed air at the required pressure as measured at the generator inlet connection. If the supply piping from the compressed air receiving tank to the generator is greater than 50 fee, increase the air supply line with one standard NPT size larger than the generator inlet size (Table 1). Table 1. Standard NPT Pipe Sizes:
Nitrogen Output Piping Requirements Nitrogen output piping should be the same size as the nitrogen discharge piping on the generator. If the length of the output piping connecting the generator to your process is greater than 50 feet, use piping one standard NPT size larger than the generator output line (Table 1). | |||||||||||||||||||||||||
| Install the Membrane Nitrogen Generator | |||||||||||||||||||||||||
![]() | WARNING! - Materials that you use to maintain, assemble and connect the nitrogen generator to supporting equipment should be rated and approved for use at the pressures generated by the generator. | ||||||||||||||||||||||||
| 1. Move unit into place with a hand truck.
2. Install batteries for the oxygen analyzer. 3. Install any supporting equipment (including air compressor, booster, air dryer or receiving tanks) according to the manufacturer's recommendations. 4. Have a qualified pipefitter install suitable piping from:
5. Any tanks that you use in conjunction with the generator should be fitted with applicable pressure safety valves. | |||||||||||||||||||||||||
| Startup and Shutdown Procedures | |||||||||||||||||||||||||
| Starting the Generator
Start the air compressor per the manufacturer's instructions before starting the nitrogen generator. Be sure that all valves from the air compressor to the generator inlet are open. A - Set Valves to Pre-Start Positions
B - Begin Flow Through the Generator
C - Monitor the System Purity and Flow
| |||||||||||||||||||||||||
| NOTE - If flow through the inlet filters becomes drastically reduced (due, for example, to excessive particulate from the air compressor) and there is an immediate need for nitrogen before a filter change can be performed, the inlet pressure regulator may be adjusted upward to as much as 95% of the inlet air pressure. After the immediate need has been fulfilled, however, the filters should be examined and changed, as necessary.
NOTE - When power is restored after a power failure, the generator automatically resumes operation. | |||||||||||||||||||||||||
| Shut Down | |||||||||||||||||||||||||
| 1. Slowly close the main shutoff (compressed air inlet) valve.
2. Turn the inlet control valve to the off position. 3. Turn the start-up purge control valve to the off position. 4. Turn the calibration control valve to the off position. 5. Press the power button ( 6. Stop the compressor. | |||||||||||||||||||||||||
![]() |
WARNING! - The generator remains pressurized after shutdown. Before performing maintenance or opening any lines you must depressurize the system to prevent injury. | ||||||||||||||||||||||||
| Depressurizing the System | |||||||||||||||||||||||||
![]() |
WARNING! - You must wear eye and hearing protection during the depressurizing process to avoid possible injury. | ||||||||||||||||||||||||
| Follow these steps before performing system maintenance.
1. Wear eye and hearing personal protection equipment. 2. Close the main shutoff (compressed air inlet) valve. 3. Turn the inlet control valve to the on position. 4. Turn the start-up purge control valve to the start-up purge position. 5. Be sure the inlet pressure gauge reads zero. 6. Turn the inlet control valve to the off position. 7. Turn the start-up purge control valve to the normal operation position. | |||||||||||||||||||||||||
Phone: (520) 799-8000 | Email: sales@tdiinternational.com © Copyright 2000-2012 TDI International, Inc. TDI Home | Catalog | Newsletter | Terms | Privacy Policy | Contact Us | Conversion Charts | Site Map | |||||||||||||||||||||||||